Xylem Flygt 40-501098 MiniCAS II 11-Pin Supervision Relay 120VAC
$490.53

Xylem Flygt 40-501098 MiniCAS II 11-Pin Supervision Relay 120VAC Product Basic Information: - Manufacturer: Flygt / Xylem Flygt
- Catalog number: 40-501098
- Non-hyphenated part number: 40501098
- Product family/series: MiniCAS II
- Product type: Pump supervision relay / monitoring relay
- Relay type: Temperature and leakage monitoring relay
- Mounting style: 11-pin socket mount
Technical Specifications: - Series: MiniCAS II
- Part number: 40-501098
- Supply voltage: 120 VAC
- Supply voltage tolerance: -15% to +15%
- Supply frequency: 50/60 Hz
- Power requirement: 5 VA
- Operating principle: Current sensing
- Sensor output voltage: 12 VDC, +/- 5%
- Normal sensor current range: 3 mA to 22 mA
- High temperature alarm condition: Less than 3 mA or sensor circuit interruption
- Leakage alarm condition: Greater than 22 mA or sensor circuit short circuit
- Leakage alarm delay: 10 seconds
- Relay contact rating: 5 A at 250 VAC
- Temperature alarm contact function: Changeover relay contacts
- Leakage alarm contact function: Changeover relay contacts
- Reset type for temperature alarm: Manual reset
- Reset options: External reset push button or supply voltage interruption
- Leakage alarm reset type: Automatic reset
- Front indication lamps: Supply, temperature alarm, and leakage alarm
- Pump communication wiring: 2-wire sensor connection
- Socket type: Standard 11-pin socket
- Compatible sensor types: Thermal switches, FLS, FLS10, and CLS sensors
- Operating temperature range: -25 to +60 °C
Product Features: - Monitors common submersible pump threats including high stator temperature and leakage
- Supports thermal switch monitoring for stator overtemperature detection
- Supports FLS leakage sensor monitoring for liquid detection in stator housing or junction box
- Supports FLS10 leakage sensor monitoring for inspection chamber applications
- Supports CLS water-in-oil sensor monitoring for oil chamber applications
- Three front indication lamps for supply, temperature alarm, and leakage alarm status
- Uses two-wire communication between the pump sensor circuit and MiniCAS II relay
- Can stop the pump or provide alarm indication depending on control wiring configuration