Simplex 553-810 Magnet Tester
Simplex 553-810 is the magnet tester that Simplex names in its 4098 Detectors, Sensors and Bases Application Manual for magnet testing of 4098 sensor bases and photoelectric detectors. It attaches to a Mr. Longarm pole, 4 ft (item 7508) or 6 ft (item 7512). Simplex treats the magnet test as a functional check during installation; smoke testing is still needed to meet NFPA requirements.
Specifications Part number 553-810 Type Magnet tester Pole attachment Mr. Longarm 4 ft (item 7508) or 6 ft (item 7512) Sensor bases named 4098-9775, 4098-9776, 4098-9777, 4098-9780, 4098-9789, 4098-9791, 4098-9792, 4098-9793 Photoelectric detectors named 4098-9601, 4098-9602, 4098-9605 Compatibility and installation notes
- Sensor bases: hold the tester 1/2 to 3/4 in. (12 to 20 mm) counterclockwise from the visible LED on the base. On MAPNET II devices a magnet test reports 255 for the current/peak value; clear peak values after testing.
- Photoelectric detectors: hold it over the \"|\" mark on the cover for 4 seconds. A detector within calibration latches into alarm with the LED on; more sensitive gives six rapid flashes then latches; less sensitive gives four slow flashes then latches; a non-functional detector gives four slow flashes and does not latch.
- Clean a detector that tests out of range, and replace it if it still reads abnormal after cleaning.
- Reset the fire alarm panel after testing to restore normal status.
Specifications from Simplex 4098 Detectors, Sensors and Bases Application Manual 574-709 Rev. AP (Portuguese edition), sections 6.3.4 to 6.3.6. Manufacturer specifications are subject to change.
Brand new in original packaging. Ships same business day from Atlanta, GA when ordered by 3 PM ET. 30-day returns. 1-year warranty.