New Schneider Foxboro DCS FCP280 RH924YA CPU Module Field Control Processor
Product is new old stock, however the LCD module has some bleed through. Appears to be a common issue. Fully functional product still!
Same day shipping, ships UPS 1-Day service. Arrives tomorrow!
Product pulled from bulk OEM packaging.
30-day Warranty
Processor Type:
• ControlProcessor: ARM® System on a Chip (SOC)
• Memory:
• 128 MBSDRAM
• 128 MBFlash Memory
• ErrorDetection: ECC for single-bit error correction and multiple-bit error detection
Process I/O Communications:
• FieldbusType: HDLC
• TransmissionRate:
• 2 Mbpsfor 200 Series FBMs
• 268 Kbpsfor 100 Series FBMs
Process I/O Capacity:
• 200Series FBMs:
• Up to 32per Expanded Fieldbus
• Up to 128FBMs over all four Expanded Fieldbuses with 200 Series FBMs
• Mixedwith 100 Series FBMs: Up to 128 FBMs, e.g., 64 100 Series and 64 200 SeriesFBMs
• 100Series FBMs:
• 64 FBMsper PIO bus/baseplate port
• Total of128 FBMs per FCP280
• CompetitiveMigration Modules: Refer to device-specific Product Specification Sheets
Memory Allocation for Blocks:
• ClassicOLUG: 15.75 MB
• EnhancedOLUG: 19.75 MB
Maximum Number of Blocks Configured:
• Total:8,000 (7,993 user-configured)
Block Executions Per Second:
• Maximum:16,000 blocks/second
Maximum Number of Blocks Processed:
• Dependson: Scan periods and block type selection
Minimum Block Processing Cycle (BPC):
• Time: 50ms
Sequence Block Size:
• Maximum:32 kB per block
Maximum Number of IPC Connections:
• Total:231
• 200Source Points
• 30 SinkPoints
• 1Internal Use Only
Maximum Number of OM Sink Lists:
• Total: 75
Maximum OM Scanner Database:
• BPC ≥ 200ms: 18,000 points
• BPC ≤ 100ms: 7,500 points
Maximum Number of OM Sink Points:
• Total:11,250
Configurable Block Periods:
• Seconds:0.05, 0.1, 0.2, 0.5, 0.6, 1, 2, 5, 6, 10, 30
• Minutes:1, 10, 60
Block Processing Cycle:
• Options:0.05, 0.1, 0.2, 0.5, 1.0 seconds
Time to Marry Fault-Tolerant Modules:
• LessThan: 0.5 seconds
Internal Diagnostics:
• Self-Checking:At power-up
• Run-TimeChecks: Includes watchdog timer and constant synchronization in fault-tolerantmode
Power Requirements:
• InputVoltage: 24 V DC (Redundant)
• Consumption:
• SingleModule: 11 W maximum
• Fault-TolerantPair: 20 W maximum
Regulatory Compliance and EMC:
• EMCDirective 2014/30/EU: EN 61326-1 Class A
Environmental Specifications:
• OperatingTemperature: -20 to 60°C (-4 to 140°F)
• StorageTemperature: -40 to +70°C (-40 to +158°F)
• RelativeHumidity: 5 to 95% (Non-condensing)
• Altitude:
• Operating:-300 to +3,000 m (-1,000 to +10,000 ft)
• Storage:-300 to +12,000 m (-1,000 to +40,000 ft)
• ContaminationClass: G3 (Harsh)
• Vibration:0.5 g (5 to 500 Hz)
Physical Specifications:
• Configuration:
• Singleprocessor module
• Fault-tolerantversion: Two processor modules with integral fault-tolerant connector
• Mounting:Device-specific 2-position baseplates (horizontal or vertical)
• Dimensions:
• Height:105 mm (4.13 in) or 116 mm (4.7 in)
• Width:51.8 mm (2.04 in)
• Depth:147 mm (5.79 in)
• Weight(Maximum): 0.8 kg (1.76 lb)
When you click on links to various merchants on this site and make a purchase, this can result in this site earning a commission. Affiliate programs and affiliations include, but are not limited to, the eBay Partner Network.