LSV Controls Emergency Power Control Model EPC-2-D
$78.99

EPC-2-D
APPLICATION
Emergency Power Control
For 0-10V & DALI Dimmable Loads
Project:
Model No.:
Comments:
In the past, emergency lights were kept on 24 hours
a day to meet life safety codes. Now, you can use a
UL 924 listed Emergency Power Control, Model
EPC-2-D, to convert normal light fixtures into
approved emergency lights. The EPC-2-D saves
energy and money while ensuring compliance with
both life safety and energy codes.
During normal operation, the same dimmer, occu-
pancy sensor, dimming panel, or lighting control
can switch and dim normal and emergency fixtures
on and off simultaneously.
During a utility power interruption, the
EPC-2-D automatically bypasses the normal
lighting controls, turning the emergency lights ON
at full brightness, regardless of dimmer position.
The EPC-2-D is ceiling or wall mounted in a junc-
tion box with a single gang plaster ring and is
usually located in the area where the emergency
fixtures are COMPATIBLE
UL
®
C US
UL924 LISTED
5
YEAR
WARRANTY
0-10 V Dimmer
Compatible
Isolated 0-10V relay contact ensures full bright-
ness during utility power interruption, regardless
of dimmer model.
Unique, Patented Automatic Diagnostic
When the room switch is turned off, the EPC-2-D
will run a 2.5 self-test routine, verifying that the
emergency power source was available and that
the EPC-2-D, ballast, and lamp(s) are all function-
ing correctly. This feature eliminates the need for
time-consuming and costly manual monthly
testing and is approved for this purpose. This
also allows the unit to be installed in remote or
inaccessible locations, because the unit does not
rely on access to its manual test switch.
Fire Alarm, Remote Test & 0-10V Dimming
Option
Utility & Emergency Power Indicator LED’s
Slim, attractive flush mount profile allows easy
access to manual test switch and LED’s.
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216
Phone: 510-352-9600 1-800-982-4587 Fax: LINE DRAWING
Normal
Utility Power
Photo-
cell D
$
Emergency Power Source
UL 1008
Transfer Switch
Or Equivalent
Neutral
Not Shown
WIRING OR
INVERTER
EMERGENCY HOT
#6 BLUE
#5 YELLOW
Emergency Light
TEST
#4 WHITE/BLUE
EMERGENCY NEUTRAL
Note: Emergency Light is also called
N/E Light or Normal/Emergency
Light by many Fire Alarm
Jumper (see
additional resources)
#1 BLACK
NORMAL RED
Normal Light (optional)
#3 WHITE
NORMAL NEUTRAL
*
Relay Panel, Power Pack, Sensor, or other (optional)
ELECTRICAL
MODEL NO.
EPC-2-D
SENSING INPUT
120V - 277V
LOAD RATING
120V - 277V (20A)
BALLAST LOAD RATING
20A (120-277V)
INCANDESCENT LOAD
1200W (120V) / 1500W Junction Box w/ single gang WEIGHT / COLOR
12 oz. / White
TEMPERATURE
32ºF - 140ºF (0ºC - 60ºC)
FLUSH MOUNTED SIZE
Single Gang Size
BODY SIZE
1.7” x 3” x 1.2” (W x H x D body)
ORDERING INFORMATION ADDITIONAL RESOURCES
5 Year Replacement Warranty
EPC-2-D Installation Sheet
FAQ Sheet
Alternative Wiring Sheet
Terms & Conditions/Warranty Information
Fire Alarm

When you click on links to various merchants on this site and make a purchase, this can result in this site earning a commission. Affiliate programs and affiliations include, but are not limited to, the eBay Partner Network.