LOC S1
Condition: Used
Description:
KEYENCE GC-S1R Safety Controller Expansion Unit / Safety Relay Output Module.
Genuine KEYENCE industrial safety control equipment removed from an industrial environment. Units are in good physical condition with normal cosmetic signs of previous installation/use. Please review all photos carefully for condition.
Model: GC-S1R
Series: KEYENCE GC Safety Controller
Type: Safety Relay Output Expansion Unit
Safety Relay Output: 1 (3a)
Resistive Load Rating: 250 VAC 6 A / 30 VDC 6 A
Inductive Load Rating: 240 VAC 2 A / 24 VDC 1 A
Made in Japan
Listing is for ONE GC-S1R module unless otherwise stated. Multiple units are available. You will receive one unit in comparable condition to those pictured.
Model
GC-S1R
Input/output points
Safety inputs
-
Safety outputs
Safety relay output
1 (3a)
AUX outputs
-
Test outputs
Safety input specifications
Input device
Input type
ON level (voltage/current)
OFF level (voltage/current)
Short-circuit current
Protection circuit
Maximum cable length
Safety output specifications
Output type
Maximum load current
Residual voltage (during ON)
Leakage current (during OFF)
Maximum capacitive load
Load wiring resistance
Protection circuit
Maximum cable length
Safety relay output specifications
Output type
Relay (3a) (Externally-protected outputs)*1
Rated load (resistance load)
250 VAC 6A / 30 VDC 6A*2
Rated load (inductive load)
240 VAC 2A (AC-15) / 24 VDC 1A (DC-13)
Relay output mechanical life
Resistance load (250 VAC 6A/30 VDC 6A): Min. 100,000 times
Resistance load (250 VAC 1A/30 VDC 1 A): Min. 500,000 times
Inductive load (AC-15: 240 VAC 2 A): Min. 100,000 times (cosø = 0.3)
Inductive load (DC-13: 24 VDC 1 A): Min. 100,000 times (L/R = 48 ms)
Maximum cable length
Max. 100 m 328.1\'
B10d
With rated load: 400,000
With low load: 2,000,000
Test output specifications
Output type
-
Maximum load current
Protection circuit
Maximum cable length
AUX output specifications
Output type
Maximum load current
Residual voltage (during ON)
Leakage current (during OFF)
Protection circuit
Maximum cable length
Applicable standards
EMC
EMS: IEC 61131-2/-6, EN61131-2/-6,EMI: IEC 61131-2, FCC Part15B Class A, ICES-003, Class A
Safety
IEC 61508, EN 61508 SIL3, IEC62061 SIL CL3, ISO/EN 13849-1:2015 Cat. 4, PL e, UL1998
Dimensions
39.6×95×90 mm 1.56\"×3.74\"×3.54\" (W×D×H)
Power supply
Power voltage
-
Power consumption
Max. 80 mA
Environmental resistance
Ambient temperature
−10 to +55 °C 14 to 131 °F (No freezing)
Relative humidity
5 to 85% (No condensation)
Storage temperature
-25 to +70 °C -13 to 158 °F (No freezing)
Operating altitude
Max. 2000 m 6561.7\'
Overvoltage category
II (III for relay output part)
Pollution degree
2
Vibration resistance
Frequency: 5 to 9 Hz, Half amplitude: 3.5 mm 0.14\"
Frequency: 9 to 150 Hz, Acceleration: 10 m/s2
10 times each in X, Y, Z directions
Shock resistance
Acceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions
Material
Polycarbonate