Honeywell R8182D1129 Triple Aquastat Relay 120V Oil Burner Control R8182D TradelineHoneywell R8182D1129 Triple Aquastat Protectorelay Controller – Oil Burner Boiler Control
The Honeywell R8182D1129 Tradeline Triple Aquastat Relay is a combination control designed for oil-fired hydronic heating systems. It integrates high limit, low limit, circulator control, and burner relay functions into one reliable control unit.
Widely used in residential and light commercial boiler systems, this controller ensures safe operation, proper water temperature regulation, and efficient burner cycling.
Technical Specifications (From Labels & Unit)
Brand: Honeywell
Series: Tradeline
Model: R8182D1129
Also marked: R8182AD
Voltage: 120V
Frequency: 60 Hz
Type: Triple Aquastat Protectorelay
High Limit Range:
130°F – 240°F
Low Limit Range (Circulator Control):
110°F – 220°F
Timing:
Approx. 45 seconds safety timing
Mounting:
Vertical Mounting (VERT. MNTG)
Configuration:
Horizontal case less well
Ignition Type:
Constant Ignition (Use C554A CAD Cell)
Functional Description
This control performs three primary functions:
High Limit Control
Shuts off burner when boiler water reaches maximum set temperature
Low Limit Control
Maintains minimum boiler temperature for domestic hot water systems
Circulator Control
Prevents circulator operation until water reaches minimum temperature
Additionally, it includes burner relay and safety timing via CAD cell flame detection.
Internal Wiring / Terminals (From Diagram)
Power Terminals: L1, L2
Thermostat Connections
Burner Circuit
Ignition Circuit
Circulator (CIRC.)
Zone Control Auxiliary Terminals: ZC / ZR
CAD Cell Connection: C554 Cad Cell
Key Features
Triple function aquastat (HI / LO / circulator)
Integrated burner relay control
Compatible with oil burner systems
CAD cell flame detection safety
45-second safety shutdown timing
Supports zone control wiring
Heavy-duty mechanical reliability
Tradeline service replacement model
Applications
Oil-fired boilers
Hydronic heating systems
Residential boiler control systems
Domestic hot water boiler systems
Burner control systems with CAD cell flame detection
Installation Notes (From Label)
Auxiliary terminals support zone control
All zones must have a common disconnect
Checkout / Testing Procedure (From Label)
Primary Relay Test:
Verify thermostat call, burner start, and power at B1
CAD Cell Test:
Check flame detection and burner operation
Limit Switch Test:
Verify proper high/low limit operation
Keywords
Honeywell R8182D1129
R8182D aquastat relay
Triple aquastat oil burner control
Boiler aquastat controller
Honeywell Tradeline aquastat
R8182AD
Oil burner primary control
Hydronic heating control
This is a Honeywell R8182D1129 triple aquastat relay used in oil-fired boiler systems. It controls burner operation, circulator pump, and water temperature limits (high and low). Compatible with CAD cell flame detection systems such as C554A. Ideal replacement for older Honeywell Tradeline aquastat controls in hydronic heating systems.
New Old Stock (NOS) – Never Installed / Never Used.
Original retail packaging is included. The item has never been installed, energized, or placed into service.Please review all photos carefully — you will receive exactly what is shown. If something is not visible in the pictures, it is not included.The original box may show shelf wear from long-term warehouse storage.
When you click on links to various merchants on this site and make a purchase, this can result in this site earning a commission. Affiliate programs and affiliations include, but are not limited to, the eBay Partner Network.