Generator Controller Engine Remote Monitoring Control Unit Original DC42DR MK4
1.Summary
This series controller is specialized for Diesel / Gasoline / Gas Genset Start, Stop, Parameters monitoring, faults-checking as well as data setting.
3.0 inch colorful LCD screen display with brand new UI design is adapted in this controller that the relative failures can be displayed directly. All the parameters can be displayed by simulated indicators and words. Besides, LCD screen can display various faults in the same time that the genset will be stopped once it can’t work smoothly.
There are Chinese/English interface options, more language can be set according to user’s request. All the parameters can be configured through the front face buttons or use programmable interface by USB\\RS485to adjust via PC. It can be widely applied for all kinds of auto control system of gensets.
2.Main Features
There arefiveModels under DC40D MK4series.
Model
USB
RS485
AMF
ABF
DC40D MK4
●
━
━
━
DC42D MK4
●
━
●
━
DC40DR MK4
●
●
━
━
DC42DR MK4
●
●
●
━
DC42DR-ABF MK4
●
●
●
●
32bit high performance single chip microcomputer.
3.0 inch 128 * 64 high-resolutionscreen LCD, Available in 16languages, user’s language set if necessary.
Adopting PC material panel, effectively waterproof, oil-proof, UV-proof, good operating feel and long service life.
AMF: Mains monitoring and AMF (Mains/Generator automatic switching control), especially suitable for the automation system composed by mains and genset.
ABF function: automatically starts and stops the genset by monitoring the backup battery pack;
Various of crank conditions (RPM, Frequency, Oil Pressure) can be chosen.
Adapt to 3P4W,1P2W,2P3W(120V/240V,50/60HZ)
Sensor can be self-defined by front face button or PC software.
USB Port: parameters can be set even without power through USBport to monitor in real time.
With RS485 communication port, can achieve “Three Remote” functions via MODBUS protocol.
Input/output function, status can be shown directly.
More categories of surface setting.
Real time clock inside: preset time operate and auto maintenance is available. Genset working plan can be set as per week or month.
Maintenance countdown function, which can set the maintenance time or date.
The black box function can save the relevant parameters of the unit when the fault alarm occurs in real time, and it is convenient to find the cause of the fault.
Has an operation log function that can save 5000 user operation records;
It has anrunningrecord function, which can save 5000 gensetrunningrecords;
Totally 6relay’s output, among which 4relay output can be self-configurable, each relay can be set as max 30 functions, besides, there are 2groups as non-contact terminals.
With 5 switchesinput, up to 10 functions optional;
3sensor simulation input connectors,and various display units can be configured.
Control Protection: Auto Start/Stop of genset, load transfer (ATS control) and perfect failure display and protection.
Standard water-proof rubber gasket. The waterproof can reach IP65.
Module design: All the connections are adapted with European connectors so that installation, connection, repair and replacement can be more easily.
Parameters
Options
Parameters
Working voltage
DC8V----36V Continuous
Power consumption
Standby:24V:MAX 1W
Working:24V:MAX 5W
AC Voltage Input
1P2W 30VAC-360VAC (ph-N)
2P3W 30VAC-360VAC (ph-N)
3P4W 30VAC-360VAC (ph-N)
Rotate speed sensor Frequency
1-10000Hz
MAX Accumulating Time
99999.9Hours(Min Store time:6min)
Fuel Relay Output
Max 5Amp DC+VE Supply voltage
Start Relay Output
Max 5Amp DC+VE Supply voltage
AUX. Output1
Max 5Amp DC+VE Supply voltage
AUX. Output2
Max 5Amp DC+VE Supply voltage
AUX. Output3
250V/5AMP Non-contact normally Openoutput
AUX. Output4
250V/3AMP Non-contact normally Closed output
Excitation output
DC+VE supply voltage
Switch value input
Available if connecting with Battery -
Battery pack voltage input
0-100VDC(only forDC42DR-ABFMK4)
USB
Type-B
RS485
Isolated Modbus-RTU protocol
Working condition
-25ºC ~+65 ºC
Storage condition
-40-85℃
Protection Level
IP65:when waterproof rubber gasket is added between controller and its panel
Insulation strength
Apply AC2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within 1min.
Overall dimension
189mm×134mm×50mm
Panel cutout
160mm×120mm
Weight
0.68Kg