Fire-Lite 411UD FireWatch 4-Channel Slave DACT Alarm Communicator Open Box NOS
$150.00

OVERVIEW Fire-Lite Alarms Fire-Watch 411UD, a compact four-channel, dual-line slave Digital Alarm Communicator Transmitter (DACT) manufactured by Honeywell. It allows an existing or new fire alarm control panel to transmit system status to an off-site monitoring facility for Central or Remote Station compliance. The 411UD is the four-channel member of the Fire-Watch 411 series and adds remote upload/download capability over the three-channel 411. This part number is DISCONTINUED by the manufacturer, as is the entire 411 family, making new old stock increasingly difficult to source for existing installations. Factory-packed surplus from a fire alarm installer inventory. TESTED & WORKING STATUS - NOT TESTED. This unit has not been powered up or bench verified.
- Sold as new old stock. The shipping carton has been opened, but the unit itself remains in its original unopened pink anti-static bag and has not been installed or wired.
- Visual inspection through the bag shows no handling marks, no scratches to the red enclosure, and clean unmarked terminal screws.
- No manufacturer warranty is offered by this / MPN: 411UD (Fire-Watch 411 Series)
- Monitoring channels: 4 inputs, individually programmable
- Channel programming options: fire alarm, fire trouble, fire supervisory, process monitoring, AC power loss, security alarm, and other fire and non-fire events
- Trigger inputs: contact closure for activation; 2.2K ELR required
- Operating voltage: 12 or 24 VDC, jumper-selectable at J4
- Current draw: 12 V standby 88 mA / 140 mA communicating; 24 V standby 64 mA / 120 mA communicating
- Telephone: dual line, rotary or touch-tone, interfaces to public switched telephone network; leased lines not required
- Reporting formats: 15, including ADEMCO Contact ID
- Relay: Form-C programmable relay output
- Indicators: Communication Fail, Channel Active, DACT Trouble
- Features: UL recognized dialer-runaway prevention; Carrier Access Code compliant with up to 20-digit Central Station numbers
- Agency listings: CSFM, MEA, UL
CONDITION Opened original Fire-Lite cartons showing noticeable handling: torn top flaps, tape repair, peeled shipping label remnants, and a torn blue routing sticker. Those blue sticker letters are warehouse handling marks, not manufacturer designations. Cosmetic carton wear only; the units inside are unused and still bagged. COMPATIBILITY Works as a slave DACT with essentially any fire alarm control panel providing dry contact outputs. The three-channel version is a separate part number (411) and lacks remote upload/download; the stand-alone version is the 411UDAC. Local programming requires the PRO-411 hand-held DACT programmer, which is NOT included. Remote programming uses the separate PK-411UD utility, also not included. WHAT'S INCLUDED - One Fire-Lite 411UD DACT in its original anti-static bag
- Original opened factory carton
- Operating and programming manual
- Factory accessory bag P/N 90503-B with end-of-line resistors and mounting screws
- NO PRO-411 programmer and NO PK-411UD software included
- No phone cord, batteries, or control panel included
INSTALLATION & LIABILITY Fire alarm and life safety equipment must be installed, programmed, and commissioned by a licensed fire alarm contractor in accordance with NFPA 72, the manufacturer's installation instructions, and all applicable local codes and authority having jurisdiction requirements. This item is sold as a surplus component only. The seller makes no representation of suitability for any specific installation and accepts no liability for installation, system performance, code compliance, or acceptance testing. Shipping Policy We ship within 3 business day of payment. All items are carefully packed. Returns 30-day returns accepted. Item must be in original condition. Contact Message us with any questions before purchasing.