DATAKOM DKG-116 Generator Manual and Remote Start Control Panel /Unit/Controller

DATAKOM DKG-116 Generator Manual and Remote Start Control Panel /Unit/Controller
$108.00

Buy Now

WE DO NOT SHIP THIS PRODUCT FOR USAGE IN THE USA.
DKG-116 MANUAL AND REMOTE START UNITThe DKG-116 is a low cost, comprehensive unit designed to start and stop a generating set both manually and remotely.The unit is suitable for both gasoline and diesel gensets. The standard unit controls gasoline engines. Diesel engine control is selected with a wire jumper connection.The unit is only available in 12V version.The manual control is made using RUN and STOP pushbuttons on the front panel. The remote control is made via REMOTE START input signal.When the engine is running, the unit monitors fault conditions and shuts-down the engine automatically in the occurrence of an alarm. The alarms are identified by a group of LEDs displaying only the first occurring one.The unit provides a set of digitally adjustable program parameters. All parameters are modified through front panel pushbuttons.FEATURES:
• Both Manual and remote control
• Generator protection
• Built in alarms and warnings
• Remote Start operation available
• True RMS measurements
• Tamper proof engine hours display
• Field adjustable parameters
• High current Fuel and Crank outputs
• Optional auxiliary output
• Optional magnetic pickup input
• Digital inputs: 4
• Survives cranking dropouts
• Sealed front panel
• Standard panel dimensions: 96x48mm
• Plug-in connection systemMEASUREMENTS:
⦁ Generator Volts: L1-N, L2-N, L3-N
⦁ Generator Volts: L1-L2, L2-L3, L3-L1
⦁ Generator Frequency
⦁ Battery VoltageOPTIONS:
- Auxiliary output (negative pulling).
- Magnetic pickup input.TECHNICAL SPECIFICATIONS:
Alternator voltage: 15 to 300 V-AC (Ph-N)
Alternator frequency: 50 or 60 Hz nominal.
Measurement Accuracy: 0.5% + 1 digit
Overspeed: nominal frequency + 14%
(+24% overshoot)
Underspeed: 30 Hz
Crank time: 10 sec.
Crank rest: 10 sec.
Crank attempts: 3
Stop timer: 10 sec.
Holdoff timer: 10 sec.
DC Supply Range: 9.0 to 16.0 V-DC
Cranking dropouts: survives 0 V for 100ms.
Typical Standby Current: 12mA-DC (display off)
Maximum Operating Current: 130 mA-DC
Fuel and Crank outputs: 10A @ 12V-DC
Auxiliary Output: 1A @ 12V-DC (negative pulling protected semiconductor output)
Magnetic pickup Input: 1.5 to 30Vpp
Operating temp.: -40°C (-40°F) to 80 °C (176°F).
Maximum humidity: 95% non-condensing.
Dimensions: 102 x 55 x 40 mm (WxHxD)
Packed weight: 140 g
Case Material: High Temp. ABS/PC (UL94-V0)
IP Protection: IP65 (front panel), IP30 (rear)
Conformity (EU directives)
-2006/95/EC (low voltage)
-2004/108/EC (EMC)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)