This BMS gateway from Automated Logic is a powerful tool for integrating and routing BACnet data. It offers high-speed performance and is designed to work with a variety of HVAC and refrigeration systems. The G5CE model is specifically designed for use with electric 24V power sources. With this BMS gateway, you can easily connect and control a wide range of HVAC and refrigeration components. Its Optiflex technology allows for seamless communication between devices, making it an ideal choice for both commercial and industrial applications. Whether you\'re looking to replace an existing gateway or upgrade your system, the Automated Logic G5CE is a reliable and efficient choice.
KEY FEATURES AND BENEFITS
BACnet Features
Supports routing between BACnet/IP, BACnet/Ethernet, and BACnet MS/TP networks
Supports up to 1,500 third party BACnet points
Supports up to two BACnet/IP networks on the Gig-E port
Includes two additional BACnet ports to support either two simultaneous BACnet MS/TP networks (up to 127 controllers each)to simultaneously route and share data across a wide range of building subsystems
Can serve as a BACnet Broadcast Management Device (BBMD), routing any BACnet broadcast messages directly to other BBMD devices on the BACnet network
Supports BACnet Foreign Device Registration (FDR)
Modbus Features
Can act as a master or slave on a Modbus serial network Can act as a server or client on a Modbus TCP/IP network
Hardware Features
Supports and executes control programs
Supports Gig-E, 1,000Mbps BACnet IP and DHCP IP
addressing
Ethernet port provides local access for system start-up and troubleshooting
Supports network captures for advanced diagnostics
Provides network statistics numerically or as trend graphs inside the WebCTRL building automation system
Supports DIN rail and screw mounting
Capacitor-backed real-time clock keeps time in the event of power failure or network interruption for up to three days
Connects seamlessly to theWebCTRL building automation system
SPECIFICATIONS
Part #
G5CE
OptiFlex BACnet Integrator
BACnet Conformance
Conforms to the BACnet Building Controller (B-BC), BACnet Router (B-RTR) Standard Device and BACnet BroadcastManagement Device (B-BBMD) as defined in BACnet 135. Tested to and listed to Protocol Revision 14 (135-2012).BTL Listing|PICS|WPSCert Conformance Certificate
Control Program Execution
Maximum number of control programs: 999 depending upon available memory.
BACnet Objects
Maximum number of BACnet objects: 12,000 for programming purposes.
Third-Party Integration
Supports up to 1,500 third-party BACnet integration points, and 25 modbus integration points
Power
24 Vac ±10%, 50–60 Hz, 50 VA 26 Vdc ±10%, 15 W
Communication
Gig-E Port
10/100/1000 BaseT Ethernet port for BACnet/IP and/or BACnet/Ethernet and/or Modbus full duplex
Serial Port 1
For communication with either of the following:
• A BACnet MS/TP network at 9,600 to 115,200 bps
• A Modbus at 1,200 to 115200 bpsAS/NZS 61000-6-3
Australia and New Zealand: C-Tick Mark
Serial Port 2
For communication with either of the following:
• A BACnet MS/TP network at 9,600 to 115,200 bps • A Modbus at 1,200 to 115,200 bps
BACnet International:
BACnet Test Laboratories (BTL) BACnet Protocol Revision, Revi
Local Access Port
Ethernet port at 10 or 100 Mbps for system start-up and troubleshooting
Rnet Port
Supports Up to 15 ZS wireless and/or ZS sensors, and one Equipment Touch or OptiPointTM interface
Power
24 Vac ±10%, 50–60 Hz, 50 VA 26 Vdc ±10%, 15 W
To mount the G5RE
Microprocessor
The G5RE must be mounted in a metal enclosure or cabinet which is properly rated for the32-bit ARM Cortex-A8, 600 MHz, processor two Ethernet controllers, and USB 2.0 host port
Environmental Range
32 to 140o F (0 to 60o C); 10 - 90% relative humidity, non-condensing
Memory
16 GBs eMMC Flash memory (120 MB available for use) and 256 MB DDR3 DRAM. User data is archived to non-volatile Flash
DIN rail mount
memory when parameters are changed, every 90 seconds, and when the firmware is deliberately shutdown or restarted.
1Push down and pull out the center tabs shown below to clear the din rail trough on the
Real Time Clock
Real-time clock keeps track of time in the event of a power failure for up to 3 States:FCC compliant to Title CFR47, Part 15, Subpart B, Class A. UL Listed, File E143900; CCN PAZX, UL916, Energy Management Equipment;AS/NZS:RCM Mark 61000-6-3;Canada:UL Listed File E143900, CCN PAZX7, CAN/CSA C22.2 No. 205 Signal Equip., Industry Canada Compliant, ICES-003, Class A; CE Mark Compliant with 2014/30/EU, and RoHS Compliant: 2015/863/EU;UKCAMark compliant with Electromagnetic Compatibility Regulations 2016 – Gov.UK and RoHS for Electrical and Electronic Equipment 2012.
Protection
Device is protected by a replaceable, fast acting, 250Vac, 2A, 5mm x 20mm glass fuse. The power and network ports comply with the EMC requirements EN50491-5-2
Plastic Rating
Fire-retardant plastic ABS, UL94-5VA
Mounting
DIN rail mounting or screw mounting