OVERVIEW
Autocall A100-0622 Digital Audio Riser Module, part no. 0742535AC. Autocall and Simplex are both Johnson Controls brands and this is the same hardware under different labels; the Simplex equivalent is 4100-0622 and the board service number is 742-535. This is a 3-to-8 channel digital audio riser interface module for 4100ES and 4100U emergency voice/alarm communications systems. It receives a digital audio input signal, decodes it, and distributes the selected audio channel within a transponder or remote panel bay. It also provides a Non-Alarm Audio input for background music and paging applications.
TESTED & WORKING STATUS
NOT TESTED. The factory carton is still sealed and the module has not been removed, inspected, powered, or connected to any panel. No functional, electrical, audio, or communication verification of any kind has been performed. Identification is based entirely on the factory PID label applied to the sealed carton. Buyers requiring verified-operational equipment should not purchase this item.
SPECIFICATIONS
- Autocall A100-0622 / Simplex 4100-0622, part no. 0742535AC, board service no. 742-535
- Function: 3-8 channel Digital Audio Riser Module with Non-Alarm Audio (NAA) input
- Receives and decodes a digital input signal carrying up to eight audio channels
- Current draw: 70 mA standby and 70 mA alarm
- NAA input level: accepts 25 VRMS, 70.7 VRMS, or 0.707 VRMS, jumper selectable at P4, with NAA volume trim at R4
- Riser distance: up to 2500 ft (762 m) from a 4100-1311 Digital Audio Controller using 18 AWG unshielded twisted pair
- Mounting: occupies 1 block, mounts in Block B, controlled by the Transponder Interface Module (TIC) or a 4100-0623 Network Audio Riser Controller Module
- Onboard configuration: DIP switch SW1 (PDI drive), SW2 (channel out selector), jumper P2 (supervision type), terminal blocks TB1 channel out, TB2 NAA in, TB3 DAR connector
- Installation instructions: 574-844
- Country of manufacture: Mexico (COO MX)
- Date code 24 358 V - day 358 of 2024. Serial factory label reads N/A
CONDITION
Unused surplus from an installer's stock. The factory carton is sealed with original tape intact and has not been opened. The module has therefore not been visually inspected and remains in its factory anti-static packaging. The carton exterior shows moderate shelf and handling wear including surface soiling, scuffing along the taped seam, minor edge crushing at one corner, and a torn label remnant on the top seam. The factory PID label is fully intact and legible. There is no indication of prior installation, return, or field handling of the module itself.
COMPATIBILITY
For use in Simplex 4100ES and 4100U fire alarm control panels and MINIPLEX transponders, and Autocall TrueAlert ES equivalents, configured for digital audio. Requires a digital audio source such as a 4100-1311 Digital Audio Controller and a controlling Transponder Interface Module or 4100-0623 Network Audio Riser Controller Module. This is the DIGITAL riser module; the analog equivalent is 4100-0621 and the two are NOT interchangeable. IMPORTANT per Johnson Controls installation instructions: do not install a digital audio riser module using the NAA interface in the same bay as an Analog Audio Controller module, and DIP switch positions 3 and 4 must remain OFF to avoid damaging the module. Verify panel executive software, module revision, and bay block availability with your Johnson Controls representative before purchase.
WHAT'S INCLUDED
- One (1) Autocall A100-0622 Digital Audio Riser Module in its sealed original factory carton
- Carton contents have NOT been verified because the carton has not been opened. Standard factory packing for this part is the module in anti-static wrap; ribbon cable, harness, mounting hardware, and printed instructions are NOT confirmed present
- No panel, no transponder cabinet, no audio controller, no programming software or tools
INSTALLATION & LIABILITY
This equipment must be installed, programmed, and commissioned by a licensed fire alarm professional in accordance with NFPA 72, the National Fire Alarm and Signaling Code, and all applicable local codes and authority having jurisdiction requirements. Nothing offered here is certified working. No bench power-up has been performed, and a bench power-up would not constitute commissioning in any case. Other items in this seller's inventory have been opened for inspection; this particular carton has not. It is the buyer's responsibility to verify module revision, panel executive software compatibility, and system configuration before purchase. No manufacturer warranty transfers with this sale and none is offered by the seller.
Shipping Policy
We ship within 3 business day of payment. All items are carefully packed.
Returns
30-day returns accepted. Item must be in original condition.
Contact
Message us with any questions before purchasing.
When you click on links to various merchants on this site and make a purchase, this can result in this site earning a commission. Affiliate programs and affiliations include, but are not limited to, the eBay Partner Network.