System Sensor RTS2 Multi-Signaling Accessory
The System Sensor RTS2 is a multi-signaling accessory for InnovairFlex 4-wire conventional duct smoke detectors. The RTS2 and the RTS2-AOS work the same way; the RTS2-AOS adds the AOS (Add-On Strobe), which this RTS2 does not include.
A key switch selects one of two connected sensors so it can be tested, reset, or both with a push button. The accessory also enables sensitivity measurements using the SENS-RDR sensitivity reader (sold separately). Two bicolored LEDs show the status of the connected duct smoke detectors.
Features
- Key switch selects sensor 1 or sensor 2 for test, reset or both
- Sensitivity readout with the SENS-RDR (sold separately)
- Built-in sounder, 85 dBA at ten feet, in a temporal or continuous pattern
- Mounts on a single- or double-gang electrical box
- Strip terminals accept 14 to 22 AWG wire
Specifications Alarm current (no strobe) 30 mA max. Alarm current (with strobe) 55 mA max. Sounder 85 dBA at ten feet Temperature range -10°C to 60°C (14°F to 140°F) Relative humidity 95% non-condensing Wire gauge 14 to 22 AWG Dimensions 4.8\" W x 5.3\" H x 1.6\" D Compatibility
The RTS2 is designed for InnovairFlex 4-wire conventional duct smoke detectors. The System Sensor manual lists the D4120, D4120W, D4P120 and D4S. The D4120 and D4120W duct detectors are available on this site.
FAQ
What is the difference between the RTS2 and the RTS2-AOS? The RTS2-AOS includes the Add-On Strobe. The RTS2 is the version without a strobe.
Can it read sensor sensitivity? Yes, with a SENS-RDR sensitivity reader, which is sold separately.